Watts to Amps Calculator

Estimate current from a load's electrical input power and supply voltage. Choose the supply type, enter a known power factor for AC and check which voltage the calculation uses.

Supply and load

Three-phase assumes a balanced supply and load.

Real electrical input power, 0–1000000000 W (or 0–1000000 kW); not VA, Wh or shaft power.

Changing units clears power; re-enter it in the chosen unit.

RMS supply voltage: 0.001–1,000,000 V. For single-phase, use voltage across the load.

Known true power factor P/S, from 0.000001 to 1; not percent or efficiency. Use 1 only when known.

Enter ungrouped digits with a leading digit and up to six decimal places. A dot or comma is decimal: 1,000 means one.

Estimated line current

Enter the supply, power, voltage and required power factor, then calculate.

Calculation happens in your browser; this tool does not upload or save your entries.

Estimate load current

  1. Choose DC, single-phase AC or balanced three-phase AC. Enter electrical input power in watts or kilowatts; for three-phase, enter the total across all three phases.
  2. Enter the voltage. For three-phase, identify whether it is measured between two lines or between a line and neutral. For AC, enter the load's known true power factor as a decimal greater than zero and no greater than one.
  3. Select Calculate current, then review the amperes, input assumptions and method. Copy includes that context. Editing an input removes the old answer; changing the power unit clears power so it can be entered in the new unit.

Use the right power, voltage and power factor

Watts and amps describe different quantities, so there is no single conversion factor. A steady 60 W DC load at 12 V draws 5 A under this model, while the same power at 24 V draws 2.5 A.

Enter real electrical input power, not watt-hours, apparent power in volt-amperes or a motor's mechanical output rating. Converting a shaft-power rating would also require efficiency information that this calculator does not infer.

Single-phase current is power divided by voltage and power factor. A balanced three-phase calculation uses total power divided by the square root of three times line-to-line voltage and power factor, or by three times line-to-neutral voltage and power factor. The answer is line current, not necessarily current in a delta-connected winding.

True power factor is real power divided by apparent power. It is not efficiency and is not entered as a percentage. A phase-angle cosine can differ from true power factor when harmonics matter. Use a compatible measured or specified value; choosing one without knowing it makes the estimate unreliable.

Check the assumptions with examples

A single-phase load taking 2300 W at 230 V with a known power factor of 1 gives 10 A. At power factor 0.8, the same real power and voltage give 12.5 A. The unity example does not mean every appliance has power factor 1.

A balanced three-phase load taking 11 kW at 400 V line-to-line and power factor 0.8 gives about 19.8464 A. That is total input power and line current; do not multiply the power or the answer by three again.

For 12000 W and power factor 1, entering 400 V line-to-line gives about 17.3205 A; entering 400 V line-to-neutral gives 10 A. Those are different voltage assumptions, not two answers for the same supply. Use the voltage basis you actually know.

What this estimate does not decide

This is a current estimate, not a wire, breaker, plug, battery, generator or circuit-capacity recommendation. Installation rules, continuous-load allowances, temperature, protection and equipment instructions require a separate qualified assessment. Do not use a zero result to decide that a circuit is de-energized.

DC assumes steady voltage and current, not a reconstructed pulsed waveform. The three-phase model assumes a balanced supply and load with compatible RMS voltage/current and true power factor. It does not calculate startup or peak current, harmonic content, phase imbalance, neutral current, motor efficiency or exported power. A single-phase appliance still uses the single-phase formula even in a building with three-phase service.

Enter ungrouped numbers with a leading digit and at most six decimal places; a single dot or comma is decimal, so 1,000 means one here. Voltage must be 0.001 to 1000000 V, power factor 0.000001 to 1, and power no more than 1000000000 W or 1000000 kW. These are software limits, not safe equipment ratings. Results use up to six significant digits, with scientific notation for very small or large currents.

Your calculation

Calculation takes place in your browser. This tool does not add input uploads or save your values between visits. Copy writes a result to the clipboard only when requested; if clipboard access is unavailable, you can copy the selected text manually. Existing site services still follow the site privacy policy.

Watts to amps questions

No. The same power can correspond to different currents at different voltages. For AC, the supply type and a compatible power factor are also needed.

Enter total real electrical input power across all three phases. The three-phase formulas already account for the balanced phases; do not multiply that total by three again.

Choose line-to-line for voltage between two lines, or line-to-neutral for voltage from a line to neutral. Do not reuse the same numeric voltage under both labels and assume the supply is unchanged. If the voltage basis is unknown, obtain the correct information before relying on the estimate.

Use 1 only when unity power factor is known for the load. Power factor is not efficiency, and a motor's shaft power is not its electrical input power. The calculator does not guess either missing quantity.

No. Current conversion does not establish safe circuit capacity or satisfy an installation code. Equipment instructions and a qualified electrical assessment must address protection, cable sizing and operating conditions separately.

It prevents a retained number from silently taking on a value one thousand times larger or smaller. Re-enter power in the selected unit, then calculate again. The other inputs remain, but the previous result is removed.

Sources and assumptions

These references explain the power relationships and the meaning of true power factor.

Educational conversion reviewed against these definitions; it is not manufacturer approval, code compliance, a safe-current certificate or a substitute for qualified electrical assessment.

Battery Runtime Calculator

Estimate how long a battery or portable power station can run an average load using Wh, Ah or mAh and an adjustable usable-energy percentage.

Open tool — Battery Runtime Calculator

Electricity Cost Calculator

Estimate flat-rate energy cost from power and time or known kWh, using your own electricity price.

Open tool — Electricity Cost Calculator
View all tools in this category